Original Industrial Spare Part
Phoenix Contact QUINT-PS/1AC/24DC/5 Retrofit PSU Legacy Systems
Verify the part, confirm the platform family, and move straight into quotation with the right commercial details.
RFQ Ready
- SKUQUINT-PS/1AC/24DC/ 5 2866750
- CategoryPLC & Industrial Automation Modules
- BrandPhoenix Contact
- SupportAvailability, lead time, condition, and shipping coordination
How Buyers Usually Use This Page
- Confirm the exact part number and platform family before sending the quote request.
- Use direct email when quantity, condition, and destination are already defined internally.
- Switch to the broader brand or category archive when you need alternates nearby.
Series Navigation
Move through the most common platform families behind this part.
Product RFQ
Send this part directly for quotation.
Include quantity, required condition, destination country, and target delivery timing. Current reference: Phoenix Contact QUINT-PS/1AC/24DC/5 Retrofit PSU Legacy Systems with SKU QUINT-PS/1AC/24DC/ 5 2866750.
Phoenix Contact QUINT-PS/1AC/24DC/5 Retrofit PSU Legacy Systems
The Phoenix Contact QUINT-PS/1AC/24DC/5 (Order No. 2866750) is a single-phase AC input, 24 VDC / 5 A output DIN-rail power supply from the renowned QUINT series — one of the most widely deployed industrial power supply platforms in global automation infrastructure. As legacy control panels age and original QUINT-series units reach end-of-life, plant engineers and maintenance teams increasingly require a verified retrofit-compatible replacement that preserves existing wiring layouts, DIN-rail footprints, and 24 VDC bus architecture without forcing a full cabinet redesign. This unit is sourced, inspected, and dispatched with a 12-month warranty to support planned maintenance windows, emergency breakdowns, and long-cycle spare-parts programs across process automation, discrete manufacturing, building management, and transportation control environments.
Whether you are replacing a failed unit in a legacy Siemens S5 or S7 control cabinet, upgrading a Rockwell Automation Allen-Bradley SLC 500 power distribution rail, or migrating a GE Fanuc Series 90 panel to a modern Ethernet-based architecture, the QUINT-PS/1AC/24DC/5 provides a stable, SFB (Static Boost) regulated 24 VDC supply that maintains output voltage under dynamic load conditions — a critical requirement when powering field I/O modules, communication gateways, and HMI panels simultaneously.
Upgrade Compatibility Table
| Parameter | QUINT-PS/1AC/24DC/5 (2866750) | Retrofit Notes |
|---|---|---|
| Input Voltage | 85–264 VAC, 1-phase | Compatible with standard single-phase industrial supply; no transformer required in most EU/US/Asia panels |
| Output Voltage | 24 VDC (adjustable 18–29.5 VDC) | Matches legacy 24 VDC bus; verify downstream device tolerance before adjusting |
| Output Current | 5 A continuous | Confirm total I/O load; if >5 A, consider QUINT-PS/1AC/24DC/10 or QUINT-PS/1AC/24DC/20 for headroom |
| DIN Rail Mounting | 35 mm DIN rail (EN 60715) | Direct drop-in for standard 35 mm rail; verify cabinet depth ≥ 65 mm |
| Terminal Type | Screw terminals, 2.5 mm² | Re-use existing wiring if conductor cross-section ≤ 2.5 mm²; re-terminate if using ferrules |
| Communication / Signaling | DC OK relay output (floating contact) | Wire DC OK to PLC digital input for power-fail alarm; compatible with most DI modules |
| Redundancy Support | Via external QUINT-ORING or diode module | Pair with QUINT-ORING/24DC/2×10/1×20 for N+1 redundancy without rewiring |
| Replacement Suggestion | Direct replacement for 2866750, QUINT-PS/1AC/24DC/5 | Also compatible as upgrade path from TRIO-PS/1AC/24DC/5 in space-constrained panels |
| Commissioning Focus | Output voltage trim, DC OK wiring, load test | Perform 30-minute burn-in at full load before returning panel to service |
| Warranty | 12 Months | Covers manufacturing defects; includes pre-shipment functional test report on request |
Retrofit Planning for Existing Automation Systems
Successful retrofit of the QUINT-PS/1AC/24DC/5 into an existing automation panel begins well before the unit arrives on site. The first step is a thorough power budget audit: list every 24 VDC consumer in the cabinet — including Phoenix Contact IB IL 24 DI 8 digital input terminals, IB IL 24 DO 4 digital output terminals, AXL F BK ETH bus couplers, MCR-SL-S-100-I signal conditioners, and any third-party 24 VDC relays or solenoid drivers — and sum their steady-state and inrush currents. If the total approaches or exceeds 4.5 A, plan to either add a second QUINT-PS/1AC/24DC/5 in a load-sharing configuration or upgrade to the QUINT-PS/1AC/24DC/10 (10 A output) to provide adequate derating margin.
Next, inspect the existing terminal block layout. In many legacy panels, the 24 VDC distribution rail feeds a mix of Phoenix Contact UK 5 N terminal blocks and grouped fuse terminal blocks. The QUINT-PS/1AC/24DC/5 uses standard screw-clamp terminals accepting conductors up to 2.5 mm². If the existing wiring uses 4 mm² conductors, plan to re-terminate with appropriate ferrules or install a short jumper to a larger terminal block. Document the DC OK relay wiring — this floating contact is typically wired to a PLC digital input (e.g., a Siemens ET 200SP DI module or an Allen-Bradley 1734-IB8 POINT I/O card) to generate a power-fail alarm in the SCADA system. Verify the PLC program logic handles the DC OK signal correctly before energizing the replacement unit.
For panels that include a Phoenix Contact QUINT-BAT/24DC/3.4AH battery module for UPS functionality, confirm that the battery module’s charge current does not push the total load above the 5 A rating. If the battery module is present, the effective available current for field devices is reduced by the battery charge current (typically 0.5–1 A). In such cases, the QUINT-PS/1AC/24DC/10 is the preferred replacement to maintain UPS functionality without derating field I/O power.
Communication infrastructure within the cabinet also requires attention. If the panel hosts a Phoenix Contact FL SWITCH 1008 managed Ethernet switch or a PROFINET media converter, these devices draw 24 VDC from the same bus. Verify that their power consumption is included in the load budget. Similarly, if a QUINT-DIODE/12-24DC/2×20/1×40 redundancy module is installed to bridge two power supply outputs, confirm that the diode module’s voltage drop (typically 0.5 V) does not push the bus voltage below the minimum threshold for connected field devices.
Finally, review the HMI panel — whether a Phoenix Contact TP 3057T touch panel or a third-party operator interface — for its 24 VDC input range. Most modern HMIs accept 18–30 VDC, but older units may have a narrower tolerance. Adjust the QUINT-PS/1AC/24DC/5 output voltage trim potentiometer to 24.0 VDC ±0.5 V before reconnecting the HMI to avoid display initialization errors caused by voltage transients during power-up.
Downtime Control During System Migration
Minimizing unplanned downtime during a power supply replacement is the primary concern for maintenance engineers working on live production lines. The recommended approach is a planned maintenance window of 2–4 hours, scheduled during a low-production shift or weekend. Before de-energizing the cabinet, export a full backup of the PLC program (including data blocks, hardware configuration, and network parameters) to a laptop running the appropriate engineering software — whether Siemens TIA Portal, Rockwell Studio 5000, or Schneider Electric EcoStruxure Machine Expert. Store the backup on an isolated USB drive and verify the checksum before proceeding.
With the cabinet de-energized and locked out per LOTO procedures, photograph the existing terminal wiring before disconnecting any conductors. Label each wire with its terminal number using adhesive markers. Remove the failed or end-of-life QUINT-PS/1AC/24DC/5 by releasing the DIN-rail locking tab and sliding the unit off the rail. Install the replacement unit, reconnect all terminals in reverse order of removal, and verify torque on each screw terminal (0.5–0.6 Nm for 2.5 mm² terminals). Re-energize the cabinet and observe the DC OK LED on the front panel — a steady green LED confirms stable output. Measure the output voltage at the distribution terminal block with a calibrated multimeter before reconnecting field devices.
Once field devices are reconnected, perform a controlled power-up sequence: energize the PLC first, allow it to complete its startup diagnostics, then enable field I/O racks one segment at a time. Monitor the SCADA system for any unexpected alarms during the first 15 minutes of operation. If the DC OK relay is wired to the PLC, verify that the power-fail alarm clears correctly in the alarm management system. Document the replacement in the panel’s maintenance log, including the new unit’s serial number, installation date, and the name of the technician who performed the work.
Retrofit Support FAQ
Q1: Is the QUINT-PS/1AC/24DC/5 (2866750) a direct drop-in replacement for the original Phoenix Contact unit?
A: Yes. The replacement unit maintains the same DIN-rail footprint, terminal layout, output voltage range, and DC OK signaling as the original 2866750. No wiring modifications are required in standard installations. Verify the output voltage setting after installation using the front-panel trim potentiometer.
Q2: Can this unit be used in a redundant power supply configuration?
A: Yes. Pair two QUINT-PS/1AC/24DC/5 units with a Phoenix Contact QUINT-ORING/24DC/2×10/1×20 redundancy module to achieve N+1 redundancy. The ORING module prevents reverse current flow between the two supplies and provides a combined output alarm signal. No PLC program changes are required for basic redundancy operation.
Q3: What pre-shipment testing is performed on this unit?
A: Each unit undergoes a functional load test at rated output current (5 A / 24 VDC) before dispatch. Output voltage regulation, ripple, and DC OK relay operation are verified. A test report is available on request. All units are shipped with a 12-month warranty covering manufacturing defects and premature failure under normal operating conditions.
Q4: How quickly can this unit be dispatched, and what is the typical lead time for bulk orders?
A: Stock units are dispatched within 1–3 business days of order confirmation. For bulk orders (10+ units), contact our sales team at sale@ninermas.com to confirm availability and lead time. We maintain safety stock of high-demand QUINT-series components to support emergency breakdown situations and planned maintenance programs.
| Product Series | Other series |
|---|---|
| Country of Origin | DE |
Catalog Continuation
More Phoenix Contact modules in the catalog.
Use the brand lane to compare nearby part numbers, platform-adjacent modules, and other inquiry-ready listings before sending your final RFQ.
SKU: QUINT-PS/1AC/48DC/5 2866679
Phoenix Contact QUINT-PS/1AC/48DC/5 2866679 Safety Power Supply
SKU: CM50-PS-120-230AC/24DC/2.5/F
Phoenix Contact CM50-PS-120-230AC/24DC/2.5/F Retrofit Power Supply
SKU: 2832564 FL HUB 16TX-ZF
PHOENIX CONTACT 2832564 FL HUB 16TX-ZF Safety-Reliable Ethernet Hub
Catalog Continuation
Alternative parts within PLC & Industrial Automation Modules.
Stay inside the same system family when you need substitutes, adjacent modules, or a broader shortlist for procurement review.