Original Industrial Spare Part
ABB TU845 3BSE021447R1 Retrofit-Compatible Terminal Unit
Verify the part, confirm the platform family, and move straight into quotation with the right commercial details.
RFQ Ready
- SKUTU845 3BSE021447R1
- CategoryPLC & Industrial Automation Modules
- BrandABB
- SupportAvailability, lead time, condition, and shipping coordination
How Buyers Usually Use This Page
- Confirm the exact part number and platform family before sending the quote request.
- Use direct email when quantity, condition, and destination are already defined internally.
- Switch to the broader brand or category archive when you need alternates nearby.
Series Navigation
Move through the most common platform families behind this part.
Product RFQ
Send this part directly for quotation.
Include quantity, required condition, destination country, and target delivery timing. Current reference: ABB TU845 3BSE021447R1 Retrofit-Compatible Terminal Unit with SKU TU845 3BSE021447R1.
ABB TU845 3BSE021447R1 Retrofit-Compatible Terminal Unit for Legacy Systems
The ABB TU845 (3BSE021447R1) is a field-proven terminal unit designed for the ABB S800 I/O platform, widely deployed across process automation, power generation, oil & gas, and chemical plant control systems. As legacy DCS installations age and original spare parts reach end-of-life, the TU845 remains a critical component for engineers managing brownfield retrofits, control cabinet upgrades, and I/O subsystem restoration projects. NINERMAS maintains verified stock of the TU845 3BSE021447R1 with full pre-shipment testing and a 12-month warranty, supporting customers who need a reliable drop-in replacement without redesigning their existing control architecture.
Upgrade Compatibility Table
| Parameter | Details |
|---|---|
| Part Number | TU845 / 3BSE021447R1 |
| Brand | ABB |
| Series | S800 I/O |
| Module Type | Terminal Unit (Screw Terminal) |
| Compatible I/O Modules | AI810, AO810, DI810, DO810, DI811, DI814, DO814, AI820, AI830 |
| Backplane Interface | S800 I/O Bus Connector |
| Mounting | DIN Rail / Panel Mount |
| Communication Compatibility | PROFIBUS DP, Modulebus (via CI840/CI854 coupler) |
| Replacement Recommendation | Direct drop-in for TU845 in existing S800 racks; verify screw terminal wiring map before swap |
| Commissioning Notes | No address configuration required on TU; module address set on I/O module. Confirm field wiring continuity after installation. |
| Warranty | 12 Months (NINERMAS) |
Retrofit Planning for Existing Automation Systems
When an S800 I/O subsystem requires partial or full restoration, the TU845 3BSE021447R1 is typically the first component to be sourced, as it serves as the physical interface between field wiring and the I/O module. Before committing to a retrofit plan, engineers should confirm the following: the existing terminal block wiring map matches the TU845 screw terminal layout; the backplane slot accepts the S800 I/O bus connector without mechanical modification; and the power supply feeding the I/O rack — commonly an ABB SD831 or SD832 24VDC power supply — provides sufficient current capacity for the expanded or restored I/O count.
In a typical S800 retrofit, the TU845 is paired with signal I/O modules such as the AI810 analog input module or the DI810 digital input module, both of which mount directly onto the terminal unit. Where analog output control is required, the AO810V2 is a common companion module. For digital output applications driving solenoids or motor starters, the DO810 or DO814 modules are frequently used alongside the TU845 in the same rack assembly.
Communication between the S800 I/O cluster and the main controller — typically an AC800M PM864A or PM866A controller module — is maintained through a fieldbus coupler such as the CI840A PROFIBUS DP coupler or the CI854A Modulebus coupler. During a retrofit, it is essential to verify that the coupler firmware version is compatible with the restored I/O configuration and that the PROFIBUS segment address assignments remain consistent with the existing PLC program. Any address conflict introduced during module replacement can cause the controller to flag I/O faults, requiring a cold restart and program reload.
For installations where the S800 rack itself has been damaged or where additional I/O capacity is needed, the TB820V2 Modulebus modem or an extended rack assembly may be introduced. In such cases, installation space within the control cabinet must be confirmed before ordering — the TU845 occupies a standard S800 slot width, but rack extensions require additional DIN rail length and cable routing clearance. Signal isolators may also be required where field wiring runs exceed recommended lengths or where ground loop interference has been identified during fault diagnosis.
HMI screens connected to the AC800M system via OPC or direct Ethernet should be reviewed after any I/O module swap to confirm that tag addresses and alarm thresholds remain correctly mapped. Where the original HMI project files are unavailable, NINERMAS can advise on documentation recovery strategies based on the controller backup archive.
Downtime Control During System Migration
Minimizing production downtime during an S800 I/O retrofit requires careful pre-staging of replacement components and a structured hot-swap or cold-swap procedure depending on the process criticality. For non-critical I/O channels, the TU845 can be replaced during a scheduled maintenance window without a full system shutdown: field wiring is transferred terminal by terminal from the old unit to the new TU845, with continuity verified at each step before the I/O module is reseated.
For critical process loops — such as those controlling reactor temperature, pressure relief, or motor protection — a parallel wiring approach is recommended. A pre-wired TU845 is installed in an adjacent slot or temporary panel, field signals are bridged across, and the I/O module is transferred only after the new terminal unit has been verified under live signal conditions. This approach keeps the control loop active throughout the physical swap and eliminates the risk of an unplanned process trip.
Before any module is removed, the existing PLC program logic should be backed up from the AC800M controller using ABB Control Builder Plus or the equivalent engineering tool. This ensures that in the event of a communication fault or unexpected controller restart during the retrofit, the original program can be reloaded without data loss. NINERMAS recommends that customers retain a copy of the I/O configuration export alongside the TU845 wiring diagram for the duration of the retrofit project.
All TU845 3BSE021447R1 units shipped by NINERMAS undergo pre-shipment functional testing, including terminal continuity verification and bus connector inspection, to confirm that the unit will perform correctly upon installation. Lead times are confirmed at the time of order, and expedited shipping is available for urgent breakdown recovery situations.
Retrofit Support FAQ
Q: Is the TU845 3BSE021447R1 a direct replacement for the original TU845 in my S800 rack?
A: Yes. The TU845 3BSE021447R1 is the standard ABB part number for the S800 screw terminal unit and is a direct mechanical and electrical replacement for any existing TU845 installation. No rack modification or address reconfiguration is required on the terminal unit itself.
Q: What I/O modules are compatible with the TU845?
A: The TU845 is compatible with the full range of S800 I/O modules that use the standard S800 bus connector, including AI810, AI820, AI830, AO810, AO810V2, DI810, DI811, DI814, DO810, and DO814. Confirm the specific module type in your existing rack before ordering to ensure the correct terminal unit variant is supplied.
Q: How do I verify wiring compatibility before installing the replacement TU845?
A: Compare the screw terminal numbering on the existing TU845 with the wiring diagram for your field instruments. The TU845 3BSE021447R1 uses a standard ABB terminal layout; any deviations in your installation should be documented before the swap. NINERMAS can provide the terminal assignment reference sheet upon request.
Q: What warranty and testing does NINERMAS provide with the TU845 3BSE021447R1?
A: Every unit is covered by a 12-month warranty from the date of shipment. Pre-shipment testing includes terminal continuity checks and bus connector inspection. Stock is available for immediate dispatch, and a test report can be provided upon request for quality-critical applications.
| Product Series | S800 |
|---|---|
| Country of Origin | SE |
Catalog Continuation
More ABB modules in the catalog.
Use the brand lane to compare nearby part numbers, platform-adjacent modules, and other inquiry-ready listings before sending your final RFQ.
SKU: 3HNA024941-002
ABB 3HNA024941-002 Safety-Reliable Paint Teach Pendant
SKU: HIEE200130R0002 AFC094 AE02
ABB HIEE200130R0002 Service-Ready Spare Part for Industrial Maintenance
SKU: AI893 3BSC690141R1
ABB AI893 3BSC690141R1 Safety-Reliable Analog Input Module