Original Industrial Spare Part
Honeywell 8C-TPOX01 51307022-175 Retrofit Wireless Backplane
Verify the part, confirm the platform family, and move straight into quotation with the right commercial details.
RFQ Ready
- SKU8C-TPOX01 51307022-175
- CategoryDCS Distributed Control Systems
- BrandHoneywell
- SupportAvailability, lead time, condition, and shipping coordination
How Buyers Usually Use This Page
- Confirm the exact part number and platform family before sending the quote request.
- Use direct email when quantity, condition, and destination are already defined internally.
- Switch to the broader brand or category archive when you need alternates nearby.
Series Navigation
Move through the most common platform families behind this part.
Product RFQ
Send this part directly for quotation.
Include quantity, required condition, destination country, and target delivery timing. Current reference: Honeywell 8C-TPOX01 51307022-175 Retrofit Wireless Backplane with SKU 8C-TPOX01 51307022-175.
Honeywell 8C-TPOX01 51307022-175 Retrofit Wireless Backplane: Legacy-Compatible Upgrade for Industrial Control Systems
The Honeywell 8C-TPOX01 (P/N 51307022-175) is a ruggedized wireless module backplane engineered for demanding industrial environments. As legacy Honeywell Experion PKS and HC900 distributed control system (DCS) installations age, the 8C-TPOX01 serves as a critical retrofit component — enabling facilities to extend the operational life of existing control architectures without committing to a full platform migration. Whether you are replacing a failed backplane in a live production line, upgrading a control cabinet to support wireless I/O expansion, or restoring a discontinued spare part to maintain system continuity, the 8C-TPOX01 provides a direct, drop-in compatible solution backed by a 12-month warranty.
This backplane is designed to interface seamlessly with Honeywell’s OneWireless network infrastructure, supporting ISA100.11a wireless communication protocol. It acts as the physical and electrical bridge between wireless field devices and the controller backplane, making it indispensable in retrofit scenarios where running new signal cables is cost-prohibitive or physically impractical. Engineers undertaking legacy system modernization will find the 8C-TPOX01 particularly valuable in applications involving remote I/O expansion, hazardous area instrumentation, and rotating equipment monitoring — all without disrupting the existing control logic or HMI display configurations.
Upgrade Compatibility Table
| Parameter | Details |
|---|---|
| SKU / Part Number | 8C-TPOX01 / 51307022-175 |
| Compatible Platform | Honeywell Experion PKS, HC900, OneWireless |
| Communication Protocol | ISA100.11a Wireless |
| Backplane Interface | Compatible with C300 Controller Backplane and Series C I/O chassis |
| Installation Form Factor | Ruggedized DIN-rail / panel-mount backplane module |
| Power Requirements | 24 VDC nominal (verify against existing cabinet power budget) |
| Terminal Wiring | Confirm terminal block pitch and wire gauge compatibility before installation |
| Module Addressing | Address assignment via Experion PKS Configuration Studio or HC Designer |
| HMI Compatibility | Compatible with Experion Station and third-party OPC-DA/UA HMI systems |
| Replacement Recommendation | Direct replacement for discontinued 51307022-175; verify firmware revision |
| Commissioning Notes | Perform wireless mesh re-pairing and I/O channel verification post-installation |
| Warranty | 12 Months from date of shipment |
Retrofit Planning for Existing Automation Systems
Successful integration of the 8C-TPOX01 into a legacy control system requires methodical pre-installation planning. Before removing the failed or obsolete backplane, engineers should document the existing rack slot assignments, module addresses, and wiring terminations. In Honeywell Experion PKS environments, the C300 Process Controller manages I/O communication through the Series C backplane infrastructure — any backplane replacement must preserve the controller’s node address and I/O channel mapping to avoid program faults on restart.
Power capacity is a primary concern. The control cabinet’s 24 VDC power supply module — often a Honeywell MC-PDOX02 or equivalent redundant power supply — must be verified to support the additional load introduced by the wireless backplane and its connected field devices. In cabinets running near capacity, a supplementary power rail or load-shedding review may be required before installation proceeds.
Terminal wiring adaptation is frequently overlooked. The 8C-TPOX01 uses a specific terminal block configuration that may differ from the legacy backplane it replaces. Technicians should cross-reference the existing field wiring schedule against the new backplane’s terminal layout, paying particular attention to shield grounding, signal polarity, and intrinsic safety barriers where applicable. In hazardous area installations, the Honeywell STT850 Smart Temperature Transmitter and similar ISA100.11a-compatible wireless field devices must be re-paired to the new backplane’s wireless access point after installation.
For facilities running mixed wired and wireless I/O architectures, the retrofit may also involve reconfiguring the Honeywell WDM (Wireless Device Manager) to recognize the replacement backplane’s MAC address and re-establish the wireless mesh topology. This process typically requires access to the Experion PKS server and should be coordinated with the control room operator to minimize process disruption. Where the existing system includes Honeywell HART Multiplexer modules or Series C Analog Input modules (MC-TAIH02) sharing the same backplane chassis, their channel configurations must be exported and re-imported after the backplane swap to preserve calibration data and alarm setpoints.
In control cabinet upgrade projects involving communication protocol migration — for example, transitioning from legacy Modbus RTU field devices to ISA100.11a wireless instruments — the 8C-TPOX01 backplane serves as the gateway anchor point. Paired with a Honeywell OneWireless Multinode (WirelessHART/ISA100 gateway), it enables a phased migration strategy where wired and wireless instruments coexist on the same Experion PKS network during the transition period, reducing the risk of simultaneous cutover failures. Signal isolators such as the Pepperl+Fuchs KFD2-STC4-Ex1.20.20 may be required at the cabinet terminal strip to protect the new backplane inputs from legacy field wiring that does not meet current signal conditioning standards.
Installation space confirmation is essential in retrofit scenarios. The 8C-TPOX01’s physical dimensions must be verified against the available rack or panel space, particularly in older control cabinets where space was allocated for a different backplane form factor. Where the original backplane occupied a dedicated chassis slot, confirm that the replacement unit’s mounting hole pattern, connector alignment, and cable routing clearance are compatible before committing to the installation.
Downtime Control During System Migration
Minimizing unplanned downtime is the primary operational concern when replacing a backplane in a live industrial control system. For the 8C-TPOX01 retrofit, a structured cutover plan should be developed and reviewed with operations, maintenance, and process engineering teams before any work begins.
The recommended approach is to perform a full configuration backup of the Experion PKS database — including controller programs, I/O channel assignments, alarm configurations, and HMI faceplates — before disconnecting any hardware. This backup serves as the recovery baseline if the replacement backplane introduces unexpected compatibility issues. Where the system supports controller redundancy via a paired C300 Redundant Controller, the switchover to the secondary controller should be executed before the backplane is removed, allowing the process to continue running on the redundant path during the hardware exchange.
For non-redundant systems, the cutover window should be scheduled during a planned maintenance shutdown or low-production period. The wireless field devices connected to the 8C-TPOX01 will lose communication during the backplane replacement and re-commissioning process — operators should place affected control loops in manual mode and confirm that safety instrumented system (SIS) interlocks are not dependent on the wireless I/O channels being replaced. After the new backplane is installed and powered, the wireless re-pairing sequence typically takes 5–15 minutes per device, depending on mesh network complexity and signal path quality.
Post-installation verification should include a channel-by-channel I/O check against the original wiring schedule, confirmation of wireless signal strength and packet error rate for each re-paired field device, and a functional test of all HMI displays and alarm annunciations associated with the replaced backplane. Where the system includes Honeywell Safety Manager integration, the safety logic engineer must confirm that the I/O replacement has not affected any safety function before returning the system to automatic control.
Retrofit Support FAQ
Q1: Is the 8C-TPOX01 (51307022-175) a direct replacement for the original Honeywell backplane in my Experion PKS system?
A: Yes. The 8C-TPOX01 with part number 51307022-175 is designed as a direct retrofit replacement for the original ruggedized wireless module backplane in Honeywell Experion PKS and HC900 installations. Before installation, verify the firmware revision compatibility with your current Experion PKS server version and confirm that the backplane’s connector type matches your existing chassis interface.
Q2: What commissioning steps are required after installing the replacement backplane?
A: After physical installation and power-up, you must re-pair all ISA100.11a wireless field devices to the new backplane through the Honeywell WDM (Wireless Device Manager). Re-import the I/O channel configuration in Experion PKS Configuration Studio, verify module addressing, and perform a full I/O functional test. HMI faceplates should be checked to confirm that all process variable displays and alarm setpoints are correctly restored.
Q3: How do I confirm wiring compatibility between the 8C-TPOX01 and my existing field terminations?
A: Cross-reference the 8C-TPOX01 terminal block layout (available in the Honeywell hardware reference manual) against your existing field wiring schedule. Pay particular attention to terminal pitch, wire gauge ratings, shield grounding points, and any intrinsic safety barrier requirements for hazardous area circuits. If the terminal configuration differs from the original backplane, a terminal adapter or re-termination at the cabinet marshalling strip may be required.
Q4: What are the inventory availability and warranty terms for the 8C-TPOX01?
A: We maintain in-stock inventory of the Honeywell 8C-TPOX01 (51307022-175) to support urgent retrofit and emergency replacement requirements. All units are supplied with a 12-month warranty from the date of shipment, covering manufacturing defects and functional failures under normal operating conditions. Pre-shipment functional testing is performed on all units. Contact our technical sales team for lead time confirmation and volume pricing.
| Product Series | Experion PKS |
|---|---|
| Country of Origin | US |
Catalog Continuation
More Honeywell modules in the catalog.
Use the brand lane to compare nearby part numbers, platform-adjacent modules, and other inquiry-ready listings before sending your final RFQ.
SKU: CC-TD0R01 51308376-175
Honeywell CC-TD0R01 51308376-175 Spare Part for Maintenance
SKU: 8C-PCNT02 51454363-275
Honeywell 8C-PCNT02 51454363-275 Spare Part for Maintenance
Catalog Continuation
Alternative parts within DCS Distributed Control Systems.
Stay inside the same system family when you need substitutes, adjacent modules, or a broader shortlist for procurement review.
SKU: CE4006P2 KJ3241X1-BA1 12P2506X102
EMERSON CE4006P2 KJ3241X1-BA1 12P2506X102 DeltaV I/O
SKU: 3BSE003127R1 DSAI130D
ABB 3BSE003127R1 DSAI130D Retrofit-Compatible Analog Input Module
SKU: BC810K02 3BSE031155R1
ABB BC810K02 3BSE031155R1 Retrofit CEX-Bus Unit Legacy
SKU: TK-IAH161 TK-OAV081 TK-PPD011