Original Industrial Spare Part

Honeywell CC-TPOX01 Spare Part for Industrial Maintenance

Verify the part, confirm the platform family, and move straight into quotation with the right commercial details.

SKU: CC-TPOX01 51306528-175 DCS Distributed Control Systems Honeywell

RFQ Ready

Pricing by RFQ

How Buyers Usually Use This Page

  • Confirm the exact part number and platform family before sending the quote request.
  • Use direct email when quantity, condition, and destination are already defined internally.
  • Switch to the broader brand or category archive when you need alternates nearby.

Series Navigation

Move through the most common platform families behind this part.

Honeywell CC-TPOX01 Spare Part for Industrial Maintenance

The Honeywell CC-TPOX01 (part number 51306528-175) is a ruggedized control module designed for use within the Honeywell Experion PKS and C300 Controller platform — one of the most widely deployed distributed control systems (DCS) in continuous process industries. As a service-ready spare part, the CC-TPOX01 plays a critical role in daily inspection routines, fault isolation, emergency replacement, annual overhaul programs, and long-term system life extension strategies across refineries, chemical plants, power generation facilities, and water treatment operations.

For maintenance engineers managing aging DCS infrastructure, having a verified, tested, and immediately available CC-TPOX01 in the spare parts inventory is not optional — it is a fundamental risk control measure. Unplanned downtime caused by a failed control module can halt production lines, trigger safety shutdowns, and result in significant financial losses. NINERMAS supplies the CC-TPOX01 with full pre-shipment electrical testing, 12-month warranty coverage, and long-term stock availability to support both emergency procurement and planned maintenance cycles.

Spare Maintenance Table

Parameter Specification / Details
Part Number CC-TPOX01 / 51306528-175
Brand Honeywell
Series Experion PKS / C300 DCS Platform
Module Type Control / I/O Interface Module
Power Supply Voltage 24 VDC (nominal, from CPPM or chassis backplane)
Communication Interface FTE (Fault Tolerant Ethernet) / C300 backplane bus
Operating Temperature 0°C to 60°C (32°F to 140°F)
Humidity Tolerance 5% to 95% RH, non-condensing
Mounting Experion I/O chassis / IOTA terminal base
Compatibility Honeywell Experion PKS R310 and above; C300 Controller series
Replacement Scope Direct replacement for failed or end-of-life CC-TPOX01 units
Pre-Shipment Testing Full electrical and functional verification
Warranty 12-Month Warranty — NINERMAS
Lead Time In stock — ships within 1–3 business days
Origin USA (Honeywell manufactured)

Maintenance Planning for Continuous Operation

When a maintenance or procurement engineer evaluates the CC-TPOX01 for replacement or stock replenishment, it is essential to assess the broader control cabinet ecosystem to prevent cascading failures and ensure a smooth restoration of normal operation.

The CC-TPOX01 interfaces directly with the Honeywell C300 Controller via the chassis backplane. Before replacing the module, engineers should verify the health of the CPPM (Control Processor Power Module), which supplies regulated 24 VDC to the I/O chassis. A degraded CPPM can cause intermittent module faults that are misdiagnosed as CC-TPOX01 failures. Similarly, the CC-TAIX11 and CC-TAOX11 analog I/O modules mounted on the same chassis should be inspected for signal drift or terminal corrosion, as these share the same backplane communication bus.

The IOTA (I/O Termination Assembly) — the terminal base on which the CC-TPOX01 is mounted — should be checked for bent pins, oxidized contacts, and secure DIN rail seating. A damaged IOTA can cause the replacement module to report faults immediately after installation, leading to unnecessary re-work. Alongside the IOTA, the FTE (Fault Tolerant Ethernet) switch connecting the C300 controller to the supervisory network should be verified for port integrity and cable continuity.

For sites running redundant C300 configurations, the CC-PCF901 fiber communication module and associated fiber patch cables should be inspected during the same maintenance window. Fiber degradation is a common hidden cause of intermittent DCS communication alarms that are often attributed to module faults. Additionally, the Honeywell UDC3500 Universal Digital Controller or standalone loop controllers in the same panel should be checked for calibration drift if they share signal references with the affected I/O loop.

From a power protection standpoint, the 24 VDC industrial power supply feeding the I/O chassis — often a Phoenix Contact QUINT or Siemens SITOP unit — should be load-tested to confirm it is not operating near its rated capacity. Overloaded power supplies are a leading cause of intermittent module resets in DCS environments. Inline fuse terminals (such as Weidmüller or Phoenix Contact fuse holders) protecting individual I/O circuits should also be inspected and replaced if discolored or showing signs of thermal stress.

Finally, the Honeywell Experion PKS Station (EPS) or operator workstation should be used to run a full diagnostic scan of the C300 node after module replacement, confirming that all I/O points are correctly mapped, alarm limits are restored, and no latent faults remain in the controller memory. Keeping a documented spare parts list that includes the CC-TPOX01, CPPM, IOTA bases, FTE switches, and analog I/O modules ensures that your maintenance team can respond to any single-point failure within the minimum possible recovery time.

Site Replacement Workflow

Replacing the CC-TPOX01 on an active Experion PKS system requires a structured approach to minimize downtime and protect process continuity:

Step 1 — Pre-Replacement Verification: Confirm the replacement CC-TPOX01 part number (51306528-175) matches the installed unit. Check the Experion system software version to ensure firmware compatibility. Download and save the current controller configuration as a backup.

Step 2 — Safe Isolation: Place the affected C300 controller in manual mode or transfer control to the redundant controller if available. Notify the control room operator before proceeding. De-energize the specific I/O chassis slot following the site’s lockout/tagout (LOTO) procedure.

Step 3 — Module Swap: Remove the faulty CC-TPOX01 by releasing the module latch and sliding it out of the IOTA base. Insert the replacement module firmly until the latch clicks. Re-energize the chassis slot and observe the module status LEDs — a solid green RUN LED confirms successful initialization.

Step 4 — System Verification: From the Experion PKS Station, navigate to the C300 node and confirm all I/O points are online and reading correctly. Verify that no new alarms have been generated. Return the controller to automatic mode and confirm process values are stable.

Step 5 — Documentation: Record the replacement date, module serial number, and post-replacement test results in the site maintenance log. Update the spare parts inventory to trigger a replenishment order for the next CC-TPOX01 unit.

Spare Parts Support FAQ

Q1: Is the CC-TPOX01 (51306528-175) supplied by NINERMAS a new or refurbished unit?
NINERMAS supplies both new and professionally refurbished CC-TPOX01 modules depending on availability. All units — regardless of condition — undergo full pre-shipment electrical and functional testing. The 12-month warranty applies equally to new and refurbished stock. The condition of the unit will be clearly stated in the order confirmation.

Q2: How do I confirm compatibility before ordering?
The CC-TPOX01 (51306528-175) is compatible with Honeywell Experion PKS systems running R310 and above, using the C300 Controller platform. To confirm compatibility, provide your Experion software version, C300 firmware revision, and IOTA base part number. NINERMAS technical support can verify compatibility before shipment to eliminate installation risk.

Q3: What does the 12-month warranty cover?
The 12-month warranty covers manufacturing defects, electrical failures under normal operating conditions, and functional non-conformance verified by pre-shipment testing. It does not cover damage caused by incorrect installation, overvoltage, physical impact, or use outside the specified environmental range. Warranty claims are processed within 5 business days of receiving the returned unit.

Q4: Can NINERMAS support long-term supply for multiple CC-TPOX01 units?
Yes. NINERMAS maintains ongoing inventory of the CC-TPOX01 and related Honeywell Experion spare parts to support both emergency single-unit procurement and planned bulk purchasing for annual maintenance programs. Long-term supply agreements with fixed pricing are available for customers managing large DCS installations. Contact our team at sale@ninermas.com to discuss volume pricing and reserved stock arrangements.

Product Series

CC-

Country of Origin

US

Catalog Continuation

More Honeywell modules in the catalog.

Use the brand lane to compare nearby part numbers, platform-adjacent modules, and other inquiry-ready listings before sending your final RFQ.

Open this lane

Catalog Continuation

Alternative parts within DCS Distributed Control Systems.

Stay inside the same system family when you need substitutes, adjacent modules, or a broader shortlist for procurement review.

Open this lane

Industrial RFQ Support

Need a fast quote for a specific part number or system family?

Send your inquiry with brand, series, quantity, condition, and destination details. We will follow up on availability, lead time, and shipping options.

CallPhone MailEmail WAChat TopBack