Original Industrial Spare Part
SIEMENS 6SW1701-0DA14 Service-Ready Spare Part for Industrial Maintenance
Verify the part, confirm the platform family, and move straight into quotation with the right commercial details.
RFQ Ready
- SKU6SW1701-0DA14(V98113-A1680-A1-4.8)
- CategoryPLC & Industrial Automation Modules
- BrandSiemens
- SupportAvailability, lead time, condition, and shipping coordination
How Buyers Usually Use This Page
- Confirm the exact part number and platform family before sending the quote request.
- Use direct email when quantity, condition, and destination are already defined internally.
- Switch to the broader brand or category archive when you need alternates nearby.
Series Navigation
Move through the most common platform families behind this part.
Product RFQ
Send this part directly for quotation.
Include quantity, required condition, destination country, and target delivery timing. Current reference: SIEMENS 6SW1701-0DA14 Service-Ready Spare Part for Industrial Maintenance with SKU 6SW1701-0DA14(V98113-A1680-A1-4.8).
SIEMENS 6SW1701-0DA14 Service-Ready Spare Part for Industrial Maintenance
The SIEMENS 6SW1701-0DA14 (V98113-A1680-A1-4.8) is a critical control board spare part designed for the SIEMENS MASTERDRIVES series of industrial variable frequency drives. For maintenance engineers managing aging drive systems on production lines, conveyor systems, pump stations, or compressor banks, this component represents a direct, service-ready replacement that minimizes unplanned downtime and restores drive functionality without requiring a full drive cabinet overhaul.
When a MASTERDRIVES unit enters a fault state — whether triggered by a control board failure, firmware incompatibility, or component aging — the ability to source an original 6SW1701-0DA14 board quickly is the difference between a two-hour recovery and a multi-day production halt. NINERMAS maintains stock of this board specifically to support emergency replacement scenarios, annual maintenance shutdowns, and proactive spare parts inventory programs for facilities running SIEMENS MASTERDRIVES MC, VC, or FC variants.
This board carries version designation V98113-A1680-A1-4.8, which is essential for compatibility verification before installation. Maintenance teams should confirm the firmware version and hardware revision of the existing drive before swapping the control board, as mismatched versions can cause parameter initialization errors or communication faults on the PROFIBUS DP or USS protocol interface.
Spare Maintenance Table
| Parameter | Details |
|---|---|
| Part Number | 6SW1701-0DA14 |
| Version / Revision | V98113-A1680-A1-4.8 |
| Brand | SIEMENS |
| Series | MASTERDRIVES (MC / VC / FC) |
| Component Type | Drive Control Board / Electronics Module |
| Origin | Germany |
| Application | Industrial variable frequency drive control, motor speed regulation, process automation |
| Compatible Environment | Industrial cabinet, panel-mount drive enclosure, IP20 internal installation |
| Communication Interface | PROFIBUS DP / USS (version-dependent) |
| Installation Type | Direct board replacement, ESD-safe handling required |
| Maintenance Recommendation | Replace during scheduled shutdown; verify firmware version before installation |
| Pre-shipment Testing | Function-tested before dispatch |
| Warranty | 12 Months |
| Availability | In stock — ready for immediate dispatch |
Maintenance Planning for Continuous Operation
Replacing the 6SW1701-0DA14 control board is rarely an isolated task. Experienced maintenance engineers know that a control board failure in a MASTERDRIVES unit is often accompanied by — or caused by — stress on adjacent components. Before returning the drive to service, a thorough inspection of the surrounding electrical environment is strongly recommended.
Start with the 24VDC auxiliary power supply feeding the control electronics. A degraded or noisy power rail is a common root cause of control board damage and will destroy a replacement board if not corrected first. Check the SIEMENS SITOP PSU100S or PSU200M power supply modules if they are part of the cabinet build. Inspect the DC bus capacitors and the power section (6SE70 series IGBT modules) for signs of thermal stress or leakage — a failing power section can send voltage spikes back into the control board.
Review the I/O terminal block wiring on the drive’s X100/X101 analog and digital I/O connectors. Loose or corroded terminals cause intermittent faults that are often misdiagnosed as control board failures. If the drive communicates via PROFIBUS DP, inspect the CBP2 communication board (6SE7090-0XX84-0FF5) for damage, as a shorted bus terminator or faulty DP connector can corrupt the control board’s communication processor.
For drives integrated into a SIMATIC S7-300 or S7-400 PLC system, verify that the PLC’s CP 342-5 or CP 443-5 PROFIBUS master module is correctly parameterized after the board swap, as the drive’s GSD file parameters may need to be re-downloaded. Check the OP7 or OP17 HMI operator panel connected to the drive for parameter backup — many sites store drive parameters on the HMI’s internal memory, which can be used to restore settings after a board replacement.
Additionally, inspect the input line reactor (4EP3 series) and output dV/dt filter if installed, as these protect both the drive and motor from switching transients. Verify the motor thermistor (PTC/KTY84) input wiring at the control board terminal — an open or shorted thermistor circuit will trigger a motor overtemperature fault immediately after restart. For sites with signal isolators on the analog speed reference input, confirm the isolator output range matches the drive’s 0–10V or 4–20mA input configuration.
Finally, check the fan unit and heat sink temperature sensor within the drive enclosure. Blocked airflow or a failed cooling fan is a leading cause of repeated control board failures in high-ambient-temperature environments. Replacing the 6SW1701-0DA14 without addressing thermal management will result in premature failure of the new board.
Site Replacement Workflow
The 6SW1701-0DA14 is designed as a direct plug-in replacement for the existing control board in compatible MASTERDRIVES units. Before beginning the replacement, isolate the drive from the AC mains supply and allow the DC bus to fully discharge — verify with a calibrated multimeter that bus voltage is below 50VDC before opening the drive enclosure.
Document the existing parameter set using the SIEMENS DriveMonitor or STARTER commissioning software before removing the old board. If the drive is equipped with a PMU (Parameterization Unit) or an OP1S operator panel, use the panel’s upload function to save parameters to the panel’s internal memory as a backup.
Remove the old control board using ESD-safe tools and wrist strap. Note the position of all ribbon cables, plug connectors, and the PROFIBUS termination switch before disconnection. Install the 6SW1701-0DA14 replacement board, reconnect all cables in the documented order, and restore the parameter set via DriveMonitor or the OP1S panel download function.
Perform a no-load test run at low speed before reconnecting the mechanical load. Monitor the drive’s fault memory (r0947/r0949) for any new fault codes during the first 30 minutes of operation. This workflow reduces total replacement time to under two hours for a trained technician, minimizing production line downtime and ensuring system compatibility is maintained without requiring a full drive recommissioning.
Spare Parts Support FAQ
Q1: Is the 6SW1701-0DA14 (V98113-A1680-A1-4.8) compatible with all MASTERDRIVES variants?
This board is specifically versioned for compatible MASTERDRIVES MC/VC/FC units that originally shipped with the V98113-A1680-A1-4.8 hardware revision. Always cross-reference the existing board’s version label before ordering. If you are unsure of compatibility, contact our technical team with your drive’s full nameplate data and we will confirm suitability before shipment.
Q2: What pre-shipment testing is performed on this spare part?
Every 6SW1701-0DA14 unit dispatched by NINERMAS is function-tested prior to shipment to verify board integrity and basic operational parameters. Units are packed in ESD-safe anti-static bags with foam cushioning to prevent transit damage. A test report is available upon request for quality-critical procurement processes.
Q3: What is the warranty coverage and what does it include?
All spare parts supplied by NINERMAS carry a 12-month warranty from the date of shipment. The warranty covers manufacturing defects and component failures under normal operating conditions. It does not cover damage caused by incorrect installation, overvoltage events, or operation outside the component’s rated environmental specifications. Warranty claims are processed with a replacement-first policy to minimize your downtime.
Q4: Can NINERMAS support long-term or recurring procurement for this part?
Yes. NINERMAS specializes in long-term spare parts supply for industrial automation components, including discontinued and hard-to-source SIEMENS MASTERDRIVES parts. We support blanket purchase orders, scheduled delivery programs, and consignment stock arrangements for maintenance departments managing large fleets of legacy drive systems. Contact our procurement team to discuss a supply agreement tailored to your maintenance cycle.
| Product Series | MASTERDRIVES |
|---|---|
| Country of Origin | DE |
Catalog Continuation
More Siemens modules in the catalog.
Use the brand lane to compare nearby part numbers, platform-adjacent modules, and other inquiry-ready listings before sending your final RFQ.
SKU: 6DR5210-0EN00-0AA0
SIEMENS 6DR5210-0EN00-0AA0 Safety-Reliable Positioner for Critical Control Sites
SKU: MMC103 6FC5210-0DA20-2AA1
Siemens MMC103 6FC5210-0DA20-2AA1 Safety-Reliable HMI for Critical Control Sites
Catalog Continuation
Alternative parts within PLC & Industrial Automation Modules.
Stay inside the same system family when you need substitutes, adjacent modules, or a broader shortlist for procurement review.